Floor Scrubber Charger Keeps Tripping the GFCI
Why a floor scrubber charger trips a GFCI outlet, how to tell a nuisance trip from a real fault, and the four GFCI models Delta-Q tested with its RC900 and RC1200 chargers.
Key takeaways
- A charger that trips the GFCI the moment you plug it in is usually a mismatch between the charger and that GFCI, not a shock hazard. Delta-Q found this with its RC900 and RC1200 scrubber chargers and blamed GFCIs that are "too sensitive to high-frequency currents."
- Delta-Q tested four self-testing GFCIs with no trips on plug-in: Leviton GFNL1-SLW, Legrand (Pass & Seymour) 2097TRNICC4, Eaton TRSGF15 and Southwire ShockShield 14880R-2. It found no such problem on its IC and QuiQ chargers.
- A GFCI trips at only a few milliamps. Fluke puts it at around 6 mA, and leakage from every device on the circuit adds up, so a charger that is fine alone can trip a shared circuit.
- A trip in the middle of a charge, or after the machine was washed, is a different case. Treat it as a real ground fault, such as water or a damaged cord, and stop resetting.
- Never remove or bypass the GFCI. In garages, sinks, laundry areas and indoor wet locations the NEC requires it, and on construction sites OSHA does.
A floor scrubber charger that trips a GFCI the instant you plug it in is most often a charger and outlet that do not get along, not a fault in the machine. Delta-Q, which makes chargers for scrubbers, sweepers and burnishers, found exactly this with its RC900 and RC1200 models. In its FAQ150 (updated February 2, 2024) it says some GFCI models may be "too sensitive to high-frequency currents, causing them to trip upon plug-in of the charger." The fix is a different GFCI, fitted by an electrician, not a way around the GFCI. A charger that trips the GFCI partway through a charge, or after the machine was washed, is a different problem. That one can be a real ground fault, and the outlet is doing its job.
Two answers circulate. One says the charger is faulty and leaking current. The other says GFCIs and chargers simply clash, so take the charger off the GFCI. The first is sometimes right and the second is never the fix. When you trip it matters most. A trip at plug-in, every time, on one outlet, points at the pairing. A random trip, a wet machine or a trip on every outlet points at a fault.
What a GFCI is and why a charger can trip it
A GFCI (ground fault circuit interrupter) is an outlet or breaker that cuts power when current leaks out of a circuit. Fluke explains how it decides. It compares the current going out on the hot wire with the current coming back on the neutral. Those two should match. If they differ, some current is taking another path, perhaps through water or a person. When the difference reaches its trip point, it cuts the power. Fluke says "most GFCIs trip at around 6 mA." ABB puts GFCI sensitivity at 5 to 6 mA. KB Electronics says a GFCI shuts the circuit off "typically no more than 5 mA," in less than a tenth of a second. A milliamp (mA) is a thousandth of an amp, so this is a tiny current.
Leakage current is a small current that flows to ground in normal use, not through a fault. Electronics cause some of it. Fluke names the cause: "surge suppression filters and capacitors on the power input of some electronic equipment." A scrubber charger is electronic equipment of this kind. Delta-Q gives a whole FAQ, FAQ108, to the high-frequency noise its chargers put out and how to filter it.
A nuisance trip is a trip with no dangerous fault behind it. Two things cause them with chargers.
- High-frequency leakage. KB Electronics studied this with motor drives, which switch power the way a charger does. It found leakage currents "typically greater than 4 kHz." It says these may trip a GFCI "because the GFCI is designed to work with 50 Hz or 60 Hz frequency inputs, not this higher value." Delta-Q's wording for its RC chargers points the same way.
- Leakage that adds up. Fluke says that with many devices on one circuit, "the leakage current is cumulative and could cause a GFCI to trip randomly." Each one is under the limit. Together they are over it.
A real ground fault is current escaping where it should not. Fluke lists "worn insulation, conductive dust, water, or other soft grounds." On a scrubber, think wet cords, a cracked plug and wash-down water.
Delta-Q's RC900 and RC1200 finding
Delta-Q's RC series was launched for "battery-powered scrubbers, sweepers, and burnishers," with full production from early 2017. The RC900 and RC1200 give 900 and 1,200 watts and come in 36 V and 48 V models.
FAQ150 is short. Here is what it says:
| Point | What Delta-Q says |
|---|---|
| Chargers affected | RC900 and RC1200 |
| Symptom | Some GFCI outlets "trip upon plug-in of the charger" |
| Likely cause | Some GFCI models "being too sensitive to high-frequency currents" (Delta-Q says "may be") |
| Tested with no trips on plug-in | Leviton GFNL1-SLW, Legrand (Pass & Seymour) 2097TRNICC4, Eaton TRSGF15, Southwire ShockShield 14880R-2 |
| What the four share | A self-testing function, and they "comply with the new version of the UL standard UL943" |
| Other GFCIs | Delta-Q does not say other models will trip. It asks you to keep the issue in mind when choosing one |
| Other Delta-Q chargers | "We have not found the same GFCI tripping issues or incompatibility on other Delta-Q charger models such as the IC-series and the QuiQ series" |
UL 943 is the safety standard for GFCIs. The "new version" took effect on June 29, 2015, according to UL. From that date GFCI outlets and breakers had to be made with a self-test function. Hubbell's sheet on the change says the device must check itself "every (3) hours or less." If it can no longer protect, it must cut power and show that it has failed. So a GFCI made before mid-2015 is an older design than the four Delta-Q tested.
One charging spot, walked through
Take a 36 V ride-on scrubber with an RC1200 charger on board. Suppose it charges in a janitor's room next to a mop sink. A sink is one of the places the NEC lists for GFCI protection, so the outlet is a GFCI. Suppose that GFCI trips the moment the plug goes in, every night.
Start with the pattern. It trips at plug-in, not an hour into the charge. That matches FAQ150 word for word. Next, look at the outlet's model number. All four GFCIs Delta-Q tested are self-testing designs, so a GFCI made before the 2015 rule is not one of them. Then try one test that changes nothing in the wiring. Plug the same charger into a different GFCI outlet, one with nothing else on its circuit. If that one holds, the charger is probably sound and the first GFCI is the problem.
From there the fix is an electrician's job. They replace the outlet with one of the four models Delta-Q tested, or move the charger to its own GFCI circuit. Nobody needs to buy a new charger. Nobody removes the GFCI either.
Change one detail and the answer changes. Suppose the same GFCI trips at random, two hours into the charge, and only on nights after the machine was hosed down. Our pressure washing guide explains why most manuals forbid hosing the machine at all. That is not FAQ150. That is water finding a path to ground, and the next section treats it as a fault.
Which kind of trip you have
Read the pattern first. Each row below follows from the sources above.
| When it trips | What it points to | What to do |
|---|---|---|
| The instant you plug in, every time, on one GFCI (RC900 or RC1200) | The pairing Delta-Q describes in FAQ150 | Try another GFCI circuit. If that holds, have an electrician fit one of the four tested models |
| At plug-in or at random, only when other gear runs on the same circuit | Leakage adding up across devices (Fluke) | Move the charger to a circuit with fewer loads, or have an electrician measure the leakage |
| Partway through a charge, after the machine was hosed, or with a damaged cord | A real ground fault: water, worn insulation, dust (Fluke) | Stop resetting. Unplug, dry and inspect the cord, plug and charger. If it repeats, call the dealer |
| On every GFCI you try, including one with nothing else on its circuit | Not the pairing in FAQ150, which concerns some GFCI models. Suspect the charger | Check the charger for a leakage fault code (below) and call the dealer |
| The GFCI will not reset, or shows a failure light, with nothing plugged in | The GFCI itself has failed or is wired wrong | Electrician replaces it. Self-testing units cut power when they fail (Hubbell) |
Two checks help any row. First, remove any extension cord and plug straight in. Delta-Q's FAQ108 says long cords, extension cords and GFCIs can change a charger's emissions, the high-frequency noise it puts back on the line. Our extension cord guide gives the gauge for each length if you must use one. Second, read the charger. Delta-Q's fault list for its IC, RC and ICL chargers names F001 "DC-DC Circuit Excessive Leakage" and F002 "PFC Circuit Excessive Leakage" as internal charger faults. Delta-Q says to remove AC and battery for at least 30 seconds and retry. If the fault comes back, it says to stop using the charger and replace it. Our charger fault codes page covers the wider families.
If a technician measures, Fluke describes how. A leakage clamp meter around the hot and neutral together shows what one circuit leaks. Around the ground wire, it shows the total flowing to ground. That turns a guess into a number.
Why the GFCI is there, and why it stays
Charging spots are often on a GFCI because of where they sit. The 2020 NEC, section 210.8(B), lists places outside homes where outlets need GFCI protection. The list includes sinks, indoor damp and wet locations, garages and accessory buildings, laundry areas, and locker rooms with showers. A scrubber charged beside a mop sink, in a wash bay or in a loading garage is likely on one of these circuits. Our flood water guide searched 12 scrubber manuals and found none that mentions GFCI, so the requirement comes from the building, not the machine.
Our guide to where to charge a floor scrubber covers the ventilation and fire code side of the same choice.
Construction sites have their own rule. OSHA 1926.404(b)(1) covers every "120-volt, single-phase, 15- and 20-ampere receptacle" that is not part of the building's permanent wiring and is used by workers. Those need GFCI protection, or the employer must run an assured equipment grounding conductor program instead. A scrubber cleaning up after the trades and charging from a temporary panel is on one of those outlets.
So the GFCI is not the thing to remove. It is the one device that cuts the power if a wet cord or a person becomes the path to ground. Fluke's advice fits every row of the table: "Instead of just resetting the GFCI, you should also investigate the cause of the trip."
Where this stops applying
FAQ150 covers two Delta-Q chargers, the RC900 and RC1200. It does not say any other GFCI will trip with them, and it found no such problem on Delta-Q's IC and QuiQ chargers. Other makers' chargers have no published list like it, so for those the pattern in the table is your guide, not the four model numbers. The trip figures above are typical values from Fluke, ABB and KB Electronics, not a test of your outlet. NEC adoption varies by state and city, and your local code and inspector decide what applies to your building. Swapping a GFCI outlet or moving a circuit is electrical work. In most places a licensed electrician should do it. If a trip comes with a burning smell, a hot plug or a wet charger, unplug it and treat it as a fault, whatever the pattern. For a charger that trips nothing but still will not charge, our battery not charging guide has the checks in order.
Frequently asked questions
Is it safe to plug a floor scrubber charger into a GFCI outlet?
Yes, and in many places it is required. A nuisance trip is an inconvenience, not a danger. The danger is removing the GFCI to stop the trips.
Why does my charger trip the GFCI only when I plug it in?
On Delta-Q's RC900 and RC1200, Delta-Q says some GFCIs are too sensitive to high-frequency currents and trip upon plug-in. Its four tested models did not.
Can I just plug the charger into a regular outlet instead?
Only where the code does not require GFCI protection, and only if the charger is sound. In wet areas, garages, sinks, laundry areas and on construction sites, a GFCI is required. Fix the pairing instead.
Does a GFCI trip mean my charger is bad?
Not by itself. If it trips on one GFCI but holds on another, the pairing is the likely cause. If it trips everywhere, or shows a leakage fault code, suspect the charger. Our battery chargers guide covers charger types and replacement.
Should several scrubbers share one GFCI circuit?
Fluke says leakage from several devices on one circuit adds up and can trip a GFCI. Where you can, give each charger its own GFCI circuit.
Sources
- Delta-Q Technologies, FAQ150 "Recommended GFCI Outlet for RC Series Chargers" (updated 2024-02-02): support.delta-q.com
- Delta-Q Technologies, FAQ108 "Reducing Electromagnetic Interference (EMI)": support.delta-q.com
- Delta-Q Technologies, Faults and Error Codes of IC/RC/ICL/XV Series: support.delta-q.com
- EE Power, "Smart Chargers for Electric Floor Care Machines" (RC900 and RC1200 launch, October 26, 2016): eepower.com
- Fluke, "Chasing 'ghost' trips in GFCI-protected circuits": fluke.com
- KB Electronics (Nidec), Bill Szatkiewicz, "Using VFDs On GFCI Devices": nidec.com
- ABB, "Understanding Ground Fault Protective Devices" (December 2021): abb.com
- UL, "UL Question Corner: Self-Testing GFCI Requirements," IAEI Magazine (October 22, 2015): iaeimagazine.org
- Hubbell, "2015 New UL GFCI Requirements": hubbellcdn.com
- Laura Hildreth, "NEC Requirements for GFCI Protection, Section 210.8," IAEI Magazine (February 6, 2020): iaeimagazine.org
- OSHA, 29 CFR 1926.404, Wiring design and protection: osha.gov