Can You Charge a Floor Scrubber in a Closet?
Can you charge a floor scrubber in a janitor closet? What 11 manuals say, the fire code rule that names floor scrubbers, and the room size and vent area per charger.
Key takeaways
- Only if the closet is ventilated enough for the charger in it. Five of the 11 manuals we read ask for a well-ventilated charging area in so many words, none names a closet, and Nilfisk's SC6000 manual says not to install a lead-acid battery "in a sealed container or enclosure."
- California's 2025 fire code names floor scrubbers in Section 309: charging must not be done in areas open to the public, combustibles stay 3 ft from the charger, and a 4-A:20-B:C extinguisher must be within 20 ft.
- For flooded batteries, the EN 62485-3 method in ZVEI's leaflet sets a free room volume of 2.5 times the hourly airflow. By our arithmetic that is about 630 cu ft for a Delta-Q IC650 and about 1,165 cu ft for an IC1200. A typical 5 by 6 ft closet holds 240 cu ft.
- A closet too small for natural ventilation can still work with a vent opening of the right size or an exhaust fan, and Tennant asks for a room at 80 F (27 C) or cooler.
- Open the battery compartment while charging. Kärcher goes further on the BD 50/50: lift off the recovery tank before charging wet batteries.
You can charge a floor scrubber in a closet only if the closet has enough air exchange for the charger in it, and most janitor closets do not. For flooded lead-acid batteries, the method in EN 62485-3 asks for a free room volume of 2.5 times the hourly airflow the batteries need. By our arithmetic that is about 630 cu ft for a small 650 W charger and about 1,165 cu ft for a 1,200 W charger, while a 5 by 6 ft closet with an 8 ft ceiling holds 240 cu ft before you subtract the machine and the shelving. A smaller room is fine with a vent opening of the right size or an exhaust fan. A closed closet with nothing is not.
Two answers circulate: anywhere with an outlet will do, or charging needs a dedicated battery room like a forklift fleet. Neither is right. The manuals that set a charging rule say "well-ventilated area," and the fire code in California names floor scrubbers outright. But the forklift room rules in OSHA's 1910.178(g) do not bind a scrubber: OSHA wrote in 1993 that sweeper and scrubber equipment "is not classified as a powered industrial truck." What decides the question is how much hydrogen the battery can give off and how fast the room clears it, and both can be calculated.
What the manuals say about where to charge
We read the charging and safety sections of 11 operator manuals and copied the location rule as written.
| Manual | Battery | Where to charge | Battery compartment while charging |
|---|---|---|---|
| Tennant T5 (9002326 Rev. 08, 10-2015) | Wet or sealed, 24 V, 20 A onboard charger | "Only charge the batteries in a well-ventilated area to prevent gas build up." Room at 80 F (27 C) or less | "Keep Battery Compartment Open When Charging." Prop up the recovery tank |
| Tennant M17 (4020655 Rev. 9, 2-2026) | Flooded or lithium | Same well-ventilated rule and 80 F limit. Lithium: "Charge battery pack in well-ventilated areas," best between 32 F and 80 F | Lift the battery compartment top cover |
| Tennant T16 (9008142) | Flooded, off-board charger | "Drive the machine to a flat, dry surface in a well-ventilated area" | "Keep covers open when charging" |
| Tennant T260 (TN7100042) | Lead-acid | "Move the machine to a well-ventilated place" | Not stated |
| Tennant T1B (9008591 Rev. 01, 07-2016) | AGM or lithium | No charging location. Store "in an open, well-ventilated, dry and clean area" | Not stated |
| Nilfisk SC6000 | Lead-acid | "Charge batteries only in well-ventilated areas, away from open flame." Do not install a lead-acid battery "in a sealed container or enclosure" | Tip the seat forward "for battery, charger access and proper ventilation" |
| Clarke CA30 20B (56091130, 7/2014) | Wet or sealed, 24 V | "Move the machine to a specified charging area." No smoking near the machine while charging | Wet batteries: "Keep all lids open" |
| Kärcher BD 50/50 C Bp Classic (59656380) | Low-maintenance wet | "Drive the machine directly to the charging station" | Remove the waste water tank first, which "prevents the accumulation of hazardous gases underneath the tank" |
| IPC CT15, CT30, CT45 | Gel, AGM or wet | Hydrogen named as a hazard of the battery compartment. Checking or topping up batteries "in a ventilated room" | Not stated |
| Betco Stealth DRS (92155-94) | 24 V, 25 A charger | "Move the machine to the battery charger." No ventilation rule | Not stated |
| Minuteman E14 (988760 Rev. A) | Gel, onboard charger | No location rule. Plug into a 115 V socket | Not stated |
Five of the 11 (four Tennant manuals and the Nilfisk) ask for a well-ventilated place to charge in so many words. IPC asks for a ventilated room for battery checks, Tennant's T1B for ventilated storage, and Clarke and Kärcher send the machine to a designated charging area. None of the 11 names a closet, and none gives an airflow figure. Trojan, which makes flooded deep-cycle batteries for scrubbers, says the same in its quick start guide: "Always charge and handle batteries in a well-ventilated area."
The two tank rules aim at the same gas: Tennant props the recovery tank up, and Kärcher takes it off the BD 50/50 because hydrogen collects beneath it. If your manual says neither, open what covers the batteries, as OSHA's forklift rule also asks: "The battery (or compartment) cover(s) shall be open to dissipate heat."
The fire code rule that names floor scrubbers
Section 309 of the 2025 California Fire Code covers "powered industrial trucks and similar equipment including, but not limited to, floor scrubbers and floor buffers." For charging it sets four rules:
- Not in public areas. "Battery charging shall not be conducted in areas open to the public." A scrubber charging in a store aisle or school corridor breaks it, however good the ventilation. It catches many retail and grocery and school fleets.
- Clearance. "Combustible storage shall be kept not less than 3 feet (915 mm) from battery chargers." Paper towel cases and mop heads stacked against the charger in a supply closet fail this one.
- Ventilation. "Ventilation shall be provided in an approved manner in battery-charging areas to prevent a dangerous accumulation of flammable gases." The code gives no airflow number. "Approved" means the fire code official accepts it.
- Extinguisher. A fire extinguisher with "a minimum 4-A:20-B:C rating within 20 feet (6096 mm) of the battery charger."
That is California's text. Other states and cities adopt their own fire codes, so ask your fire marshal which edition applies before you build a charging room.
How much air a charging scrubber needs
ZVEI, the German electrical industry association, publishes a leaflet that applies EN 62485-3, the safety standard for traction battery installations. It gives the airflow needed to keep hydrogen below its lower explosion limit of 4 percent by volume:
Q = 0.055 × n × Igas
Q is airflow in cubic meters per hour, n is the number of cells (12 for a 24 V battery, 18 for 36 V) and Igas is the charger's final charging current in amps. The charger maker should supply Igas. If it does not, the leaflet says to use "at least 40% of the maximum charging current" from the charger's nameplate. Natural ventilation counts only if the free room volume, meaning the room minus everything in it, is at least 2.5 times Q, with inlet and outlet openings each of at least 28 × Q square centimeters.
We ran those numbers for the onboard chargers on real scrubbers. Charger currents come from the Tennant T5 manual, the Betco Stealth manual and Delta-Q's IC Series specification sheet, and Igas uses the 40 percent fallback.
| Charger | Max output | Airflow needed | Free room volume for natural ventilation | Each vent opening (inlet and outlet) |
|---|---|---|---|---|
| Tennant T5 onboard, 24 V | 20 A | 5.3 m³/h (3.1 cfm) | 466 cu ft (13.2 m³) | 23 sq in (148 cm²) |
| Betco Stealth DRS charger, 24 V | 25 A | 6.6 m³/h (3.9 cfm) | 583 cu ft (16.5 m³) | 29 sq in (185 cm²) |
| Delta-Q IC650, 24, 36 or 48 V | 27, 18 or 13.5 A | 7.1 m³/h (4.2 cfm) | 629 cu ft (17.8 m³) | 31 sq in (200 cm²) |
| Delta-Q IC900, 24 or 36 V | 37.5 or 25 A | 9.9 m³/h (5.8 cfm) | 874 cu ft (24.8 m³) | 43 sq in (277 cm²) |
| Delta-Q IC1200, 24, 36 or 48 V | 50, 33 or 25 A | 13.2 m³/h (7.8 cfm) | 1,165 cu ft (33.0 m³) | 57 sq in (370 cm²) |
The table is our arithmetic. It assumes a flooded battery and the 40 percent fallback, which is the conservative case. Voltage barely matters: a 36 V charger pushes fewer amps through more cells, so the gas tracks the charger's power. Two scrubbers on two chargers in one room need the sum of both rows, because the leaflet says to assume every battery is gassing at once.
Now hold the table against a real closet. A 5 by 6 ft room with an 8 ft ceiling is 240 cu ft, which is too small for natural ventilation even with the T5's charger, before the machine takes up any of it. An 8 by 10 ft room is 640 cu ft, which clears the T5, the Stealth and the IC650 if it is mostly empty, but not an IC900 or IC1200.
The airflow figures are small, a few cubic feet per minute. So the practical fix for a small closet is not a battery room. It is a louvered door or a pair of vents of the size in the last column, or an exhaust fan to the outside. The leaflet places the inlet near the floor and the outlet "high as possible," at least 2 m (6.6 ft) apart if both are on one wall, and counts a door only if it is "constantly open during the charging process." Hydrogen is lighter than air, which is why the outlet goes high.
What happens in a closet with no air exchange
The leaflet puts the gas at "0.450 liter hydrogen" per hour for every ampere of final charging current, which works out per cell. A T5 charging with the 40 percent fallback current releases about 43 liters of hydrogen an hour across 12 cells. In a perfectly sealed 240 cu ft closet, which holds about 6,800 liters, 4 percent is 272 liters, reached in about 6 hours. With an IC1200 at full gassing it is about 2.5 hours.
That is a worst case, since real closets leak through door gaps. But Kärcher puts the BD 50/50's average charging time at 10 to 15 hours, longer than either figure, and the leaflet says gassing rises as the battery fills, until in the final phase "almost the entire charging current" goes into gas. That is why the manuals say "well-ventilated" rather than "not sealed."
The leaflet adds a rule that ventilation alone cannot satisfy. Near the battery, hydrogen may not be diluted yet, so EN 62485-3 asks for 0.5 m (about 20 in) of clear air around every cell opening, with no open flames, sparks, arcs or glowing objects inside it and no surface hotter than 300 C. Keep light switches, wall outlets and shop heaters out of that space around the open battery compartment. The plug is a spark source as well: Tennant's T1B and T260 manuals both say not to pull the DC cord while the charger is running, because arcing may result.
Battery type changes the answer
- Flooded (wet) lead-acid. The table applies as written. These batteries also need watering, and an equalizing charge is a deliberate overcharge that gasses even more, so never equalize in a closed room.
- AGM and gel. The real Igas can be far lower than the 40 percent fallback. In the ZVEI leaflet's own example, a 300 Ah gel battery on its charger has an Igas of 3.6 A, against 21 A for a 420 Ah flooded one. Ask your charger maker for the Igas of the profile you run, and see our battery charger guide for why that profile must match the battery.
- Lithium. No hydrogen in normal charging, but Tennant still asks for a well-ventilated area for the M17 lithium pack, and for best results between 32 F and 80 F. The T1B manual says that if a lithium battery "emits an unusual odor" or gets excessively hot, move the machine to a ventilated area and call service. If ventilation is the obstacle, lithium conversion covers the costs.
Where this stops applying
- Fleets and battery rooms. Several machines on several chargers add up quickly, and a room built for that should be designed to EN 62485-3 or your local code with the charger maker's Igas figures, not with this table.
- Forklift-style rules. OSHA's 1910.178(g) charging rules do not bind scrubbers, but your insurer or safety program may adopt them anyway.
- Hazardous locations. Charging in a classified area is a separate question, covered in our guide to hazardous location floor scrubbers.
- The outlet. A charger at the end of a long extension cord is not a charging station. See extension cords for floor scrubbers for gauge limits and the fixed-wiring rule.
Frequently asked questions
Is it safe to charge a floor scrubber overnight in a janitor closet?
Only if the closet is ventilated for the charger in it. A typical 240 cu ft closet is too small for natural ventilation with any charger in our table. Add vents of the listed size or an exhaust fan, open the battery compartment and keep combustibles 3 ft from the charger.
Do sealed AGM scrubber batteries need ventilation when charging?
Yes. Tennant's T5 manual gives the same well-ventilated rule for its sealed and wet batteries alike. They can need much less air than our table, which assumes flooded cells, so ask the charger maker for the Igas of your AGM profile and run the formula with it.
Sources
- ZVEI information leaflet No. 14, Ventilation of battery charging rooms for lead traction batteries (May 2020): zvei.org
- 2025 California Fire Code, Section 309, Powered Industrial Trucks and Equipment: gocodebook.com
- 29 CFR 1910.178(g), changing and charging storage batteries: law.cornell.edu
- OSHA standard interpretation, June 8, 1993, sweeper/scrubber equipment and powered industrial trucks: osha.gov
- Delta-Q IC Series Industrial Battery Chargers specification sheet: crossco.com
- Tennant T5 Operator Manual 9002326 Rev. 08 (10-2015): tennantco.com
- Tennant M17 Operator Manual 4020655 Rev. 9 (2-2026): tennantco.com
- Tennant T16 Operator Manual 9008142: thesweeper.com
- Tennant T260 Operator Manual TN7100042: tennantco.com
- Tennant T1B Operator Manual 9008591 Rev. 01 (07-2016): tennantco.com
- Nilfisk Advance SC6000 Operator Manual: sweeperland.com
- Clarke CA30 20B Operator's Manual, Form 56091130 (7/2014): caliberequipment.com
- Kärcher BD 50/50 C Bp Classic Operating Instructions 59656380: kaercher-media.com
- IPC CT15, CT15R, CT30, CT45, CT46 Operations Manual: ipcworldwide.com
- Betco Stealth DRS 26/32 manual 92155-94: elitemetaltools.com
- Minuteman E14 User Manual 988760 Rev. A: minutemanintl.com
- Trojan Battery, Flooded Battery Quick Start Guide: ressupply.com